Jane Lew PSD
EPA’s and West Virginia’s records have results for 3 contaminants in its water; 2 were found.
Serves 1,440 people · Surface water bought from another system · Jane Lew, WV
- Serves
- 1,440 people
- Connections
- 689
- Water source
- Surface water bought from another system
- Based in
- Jane Lew, WV
- County
- Lewis
- Owner
- Local government
The ZIP code it serves
The short answer
None of the results here is above a limit in force today. That covers nitrate, arsenic and other regulated chemicals, plus lead and copper, not everything. No health-based violations on file since 2016.
What was found
Where these results come from, and when
Total trihalomethanes (TTHM) and haloacetic acids (HAA5): West Virginia’s own results, samples taken from March 2, 2020 to Sept. 15, 2026, with EPA’s 2012 to 2019 file for earlier years.
Below EPA’s limits, 2 results
- Legal limit (MCL):
- Enforceable. The most a utility may deliver.
Total trihalomethanes (TTHM), Legal limit 80 ppb; highest yearly average 60.3 ppb
Highest yearly average, 2020 to 2026 · 2026 average: 49 ppb · Forms or is added in treatment
Averaged by year, the highest was 60.3 ppb, in 2022, below EPA’s legal limit of 80 ppb. Its highest single sample was 94.2 ppb. In 2026, the latest year on file, its four samples averaged below the limit. EPA recorded no violation for total trihalomethanes (TTHM) at this utility since 2020.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 78.9 ppb, in 2015.
What handles it
- NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
- NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
Haloacetic acids (HAA5), Legal limit 60 ppb; highest yearly average 37.4 ppb
Highest yearly average, 2020 to 2026 · 2026 average: 23 ppb · Forms or is added in treatment
Averaged by year, the highest was 37.4 ppb, in 2021, below EPA’s legal limit of 60 ppb. Its highest single sample was 60 ppb. In 2026, the latest year on file, its three samples averaged below the limit.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 46.7 ppb, in 2017.
What handles it
No certification claim covers this compound yet.
One compound tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
- Lead
Violations since 2016
No health-based violations on file with EPA since 2016. There are 9 monitoring or reporting violations: a sample missed, late or not reported. EPA’s file runs to 2026 Q3, so a notice your utility sent since then may not be here yet.
What this report can’t tell you
Everything else. Total trihalomethanes (TTHM) and haloacetic acids (HAA5) results here are West Virginia’s own from 2020 on, with EPA’s national file for 2012 to 2019. Jane Lew PSD’s own annual report, which it must send you every year, has the contaminants this page does not show.
Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.
What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.
Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; West Virginia’s results run from March 2, 2020 to Sept. 15, 2026.
Testing your own tap
What to test for at your tap
- Lead and copper. Both come mostly from a building’s own service line, solder and faucets, so a utility’s numbers can’t tell you yours. Jane Lew PSD’s latest lead sampling in EPA’s records, 2023 to 2025, had a 90th percentile of 0 ppb across the homes it sampled. The action level is 15 ppb, dropping to 10 ppb in November 2027, and EPA’s health goal for lead is zero. About lead.
The 3 labs West Virginia certifies closest to the area Jane Lew PSD serves, or a kit by mail
The 3 labs West Virginia certifies closest to the area Jane Lew PSD serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.
Sturm Environmental Services
Bridgeport, WV · about 16 miles
Certified for bacteria
Pace Analytical Services, LLC - Morgantown WV
Morgantown, WV · about 41 miles
Certified for bacteria
Microbac Laboratories Inc., Ohio Valley Division
Marietta, OH · about 57 miles
Certified for nitrate, lead and copper, metals, minerals and other inorganics, organic chemicals, PFAS
Or test by mail
Tap Score sells lab tests as kits you fill at your tap and mail back. The sample goes to Tap Score’s lab, not one near you, so check that West Virginia certifies it for the test you want.
Tap Score
- Lead and Copper Water Test, with a pH test strip: $55
- Essential City Water Test, 25 metals, 4 minerals, nitrate, fluoride, hardness and pH: $189
Return shipping included.
Tap Score says each kit ships to “an accredited laboratory” but doesn’t name it, so TapBuff can’t check it against West Virginia’s list.
Prices from Tap Score’s own store on Oct. 22, 2026.
What to do now
- Decide if you want a filter at allA filter for taste or chlorine is a preference, not a need. The standards say what each kind can do.NSF/ANSI standards, decoded
- Get the utility’s own reportJane Lew PSD must send you a water quality report every year. It covers contaminants this page does not show.How to read it
- Test your own tap for leadIts latest lead sampling found none at the 90th percentile, but your own service line, solder and fixtures decide the lead at your faucet.Lead in your water: what to do
Sources
- EPA UCMR 5 occurrence data, file of Oct. 15, 2026
- EPA SDWA bulk download (SDWIS federal data), 2026 Q3
- West Virginia Department of Health, Drinking Water Viewer, results from Jan. 3, 2020 to Oct. 15, 2026, read Oct. 25, 2026
- EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, file of Feb. 5, 2024
- Certified labs: West Virginia Office of Laboratory Services, laboratory certified parameter list, read Oct. 11, 2026; distances from the Census 2020 ZIP code tabulation area gazetteer
- Limits and goals: each contaminant’s page, with its EPA source.
- How this page is built: methodology.
PWSID WV3302103. Rebuilt from EPA data on Oct. 25, 2026.