Skip to content
TapBuff

Westview MHP

What EPA’s and Ohio’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
450 people
Connections
226
Water source
Groundwater
Based in
Chardon, OH
County
Wayne
Owner
Private
The ZIP code it serves

44230

The short answer

1 result is above EPA’s legal limit, and 1 more is above the health goal. The worst: Copper, above the action level. 3 health-based violations since 2016.

What handles it

What was found

Lead and copper: EPA SDWIS monitoring periods ending 2025. Copper at 37.5 mg/L (2004) is left out of this report: it is one of the results Ohio sent EPA in 2006, all at µg/L magnitudes though EPA’s file marks them mg/L.

Nitrate, haloacetic acids (HAA5), fluoride, total trihalomethanes (TTHM), chromium (total) and arsenic: Ohio’s own results, samples taken from April 29, 2020 to Oct. 14, 2025, with EPA’s 2012 to 2019 file for earlier years.

Above the legal limit1

Copper

Comes from pipes, often your own

Above the action level

2.5ppm

90th percentile, 2025

In the latest period, 9 in 10 homes sampled were at or below 2.5 ppm, above EPA’s action level of 1.3 ppm.

What handles it

Above the health goal1

Lead

Comes from pipes, often your own

Above the health goal

1.4ppb

90th percentile, 2026

In the latest period, 9 in 10 homes sampled were at or below 1.4 ppb, below EPA’s action level of 15 ppb. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.

What handles it

Below EPA’s limits5

Nitrate

Comes from the source

Below EPA’s limits

2.7ppm

Highest sample; found in 11 of 13

2025 average: 1.1 ppm

The highest sample, in 2021, was 2.7 ppm, below EPA’s legal limit of 10 ppm. In 2025, the latest year on file, its two samples averaged 1.1 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 3.4 ppm, in 2012.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

10.7ppb

Highest yearly average, 2020 to 2025

2025, one sample: 5.8 ppb

Averaged by year, the highest was 10.7 ppb, in 2024, below EPA’s legal limit of 60 ppb. In 2025, the latest year on file, its one sample was 5.8 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 15.1 ppb, in 2017.

What handles it

No certification claim covers this compound yet.

Fluoride

Forms or is added in treatment

Below EPA’s limits

0.26ppm

Highest yearly average, 2022 to 2025

2025 average: 0.11 ppm

Averaged by year, the highest was 0.26 ppm, in 2022, below EPA’s legal limit of 4.0 ppm. Its highest single sample was 0.3 ppm. In 2025, the latest year on file, its two samples averaged 0.11 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 0.98 ppm, in 2019.

What handles it

Total trihalomethanes (TTHM)

Forms or is added in treatment

Below EPA’s limits

4.8ppb

Highest yearly average, 2020 to 2025

2025, one sample: 2.2 ppb

Averaged by year, the highest was 4.8 ppb, in 2021, below EPA’s legal limit of 80 ppb. Its highest single sample was 9.6 ppb. In 2025, the latest year on file, its one sample was 2.2 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 40.5 ppb, in 2017.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Chromium (total)

Comes from the source

Below EPA’s limits

2.0ppb

Highest yearly average, 2022 to 2025

Averaged by year, the highest was 2.0 ppb, in 2025, below EPA’s legal limit of 100 ppb. Its highest single sample was 4.0 ppb. That was also the latest year on file.

What handles it

One compound tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Arsenic

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

  • NSF/ANSI 53

    Claims: Copper Reduction, Lead Reduction

    For: Copper, Lead

  • NSF/ANSI 58

    Claims: Copper Reduction, Lead Reduction

    For: Copper, Lead

At the tap, or for the whole house?

Lead and copper usually come from pipes and fixtures inside or near your home. A whole-house system sits where water enters, so it cannot catch what your own plumbing adds after it. For those, the filter that counts is the one at the tap. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

Compare five-year costs

The best water filters for lead, ranked

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
Lead and Copper RuleWater chemistry used to keep pipes from corroding was outside the required range.EPA: WQP Entry Point/Tap Treatment Technique Non-ComplianceJan. 1, 2025 to June 30, 2025—Resolved
Lead and Copper RuleWater chemistry used to keep pipes from corroding was outside the required range.EPA: WQP Entry Point/Tap Treatment Technique Non-ComplianceJuly 1, 2022 to Dec. 31, 2022—Resolved
Lead and Copper RuleWater chemistry used to keep pipes from corroding was outside the required range.EPA: WQP Entry Point/Tap Treatment Technique Non-ComplianceJan. 1, 2018 to June 30, 2018—Resolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 9 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Nitrate, haloacetic acids (HAA5), fluoride, total trihalomethanes (TTHM), chromium (total) and arsenic results here are Ohio’s own from 2020 on, with EPA’s national file for 2012 to 2019. Westview MHP’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Ohio’s results run from April 29, 2020 to Oct. 14, 2025.

Testing your own tap

Westview MHP’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Ohio certifies.

The 3 labs Ohio certifies closest to the area Westview MHP serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Eurofins Cleveland

    Barberton, OH · about 5 miles

    Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics

    (330) 497-9396

  • American Analytical Laboratories, Inc.

    Akron, OH · about 11 miles

    Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics

    (330) 535-1300

  • Alliance Technical Group, LLC-Akron

    Cuyahoga Falls, OH · about 16 miles

    Certified for nitrate, lead and copper, metals, minerals and other inorganics, organic chemicals, disinfection byproducts, PFAS, radioactivity

    (330) 253-8211

All 76 certified labs for Ohio

Sources