Skip to content
TapBuff

Avon Mobile Home Park

What EPA’s and Ohio’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
138 people
Connections
74
Water source
Groundwater
Based in
Akron, OH
County
Summit
Owner
Private
The ZIP code it serves

44685

The short answer

Nothing in EPA’s and Ohio’s records for this utility is above a health goal. That covers nitrate, arsenic and other regulated chemicals, plus lead and copper, not everything. No health-based violations on file since 2016.

What was found

Lead and copper: copper at 70 mg/L (2005) and copper at 71.5 mg/L (2004) are left out of this report: they are among the results Ohio sent EPA in 2006, all at µg/L magnitudes though EPA’s file marks them mg/L.

Total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, arsenic, chromium (total) and nitrate: Ohio’s own results, samples taken from Sept. 2, 2020 to Sept. 24, 2025, with EPA’s 2012 to 2019 file for earlier years.

Below EPA’s limits3

Total trihalomethanes (TTHM)

Forms or is added in treatment

Below EPA’s limits

21.7ppb

Highest yearly average, 2020 to 2025

2025: not found

Averaged by year, the highest was 21.7 ppb, in 2020, below EPA’s legal limit of 80 ppb. In 2025, the latest year on file, it wasn’t found in its one sample. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 14.2 ppb, in 2018.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

9.2ppb

Highest yearly average, 2020 to 2025

2025: not found

Averaged by year, the highest was 9.2 ppb, in 2023, below EPA’s legal limit of 60 ppb. In 2025, the latest year on file, it wasn’t found in its one sample. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 8.3 ppb, in 2018.

What handles it

No certification claim covers this compound yet.

Fluoride

Forms or is added in treatment

Below EPA’s limits

0.33ppm

Highest yearly average, 2022 to 2025

Averaged by year, the highest was 0.33 ppm, in 2025, below EPA’s legal limit of 4.0 ppm. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 0.33 ppm, in 2016.

What handles it

4 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Arsenic
  • Chromium (total)
  • Lead
  • Nitrate

Violations since 2016

No health-based violations on file with EPA since 2016. There is 1 monitoring or reporting violation: a sample missed, late or not reported.

What this report can’t tell you

  • Everything else. Total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, arsenic, chromium (total) and nitrate results here are Ohio’s own from 2020 on, with EPA’s national file for 2012 to 2019. Avon Mobile Home Park’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Ohio’s results run from Sept. 2, 2020 to Sept. 24, 2025.

Testing your own tap

Avon Mobile Home Park’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Ohio certifies.

The 3 labs Ohio certifies closest to the area Avon Mobile Home Park serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • American Analytical Laboratories, Inc.

    Akron, OH · about 9 miles

    Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics

    (330) 535-1300

  • Canton Water Laboratory

    Canton, OH · about 10 miles

    Certified for bacteria, nitrate, minerals and other inorganics

    (330) 489-3035

  • Canton City Health Department

    Canton, OH · about 11 miles

    Certified for bacteria

    (330) 489-3231

All 76 certified labs for Ohio

Sources

PWSID OH7700312. Rebuilt from EPA data on Oct. 18, 2026.