Skip to content
TapBuff

Pocantico Hills Water District

What EPA’s and New York’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
329 people
Connections
94
Water source
Surface water
Based in
Mount Pleasant (T), NY
County
Westchester
Owner
Local government
The ZIP code it serves

10549

The short answer

1 result is above EPA’s legal limit. The worst: Haloacetic acids (HAA5), above the legal limit. 9 health-based violations since 2016.

What was found

Haloacetic acids (HAA5), total trihalomethanes (TTHM), nitrate and arsenic: New York’s yearly summaries per water system, 2020 to 2024, with EPA’s 2012 to 2019 file for earlier years.

Fluoride, chromium (total) and uranium: EPA’s compliance monitoring file, samples taken from Sept. 27, 2012 to Nov. 4, 2019. Newer results are in the utility’s annual water quality report.

Above the legal limit1

Haloacetic acids (HAA5)

Forms or is added in treatment

Above the legal limit

60.6ppb

Highest yearly average, 2020 to 2024

2024 average: 40.5 ppb

Averaged by year, the highest was 60.6 ppb, in 2021, above EPA’s legal limit of 60 ppb. Its highest single sample was 106 ppb. In 2024, the latest year on file, it averaged 40.5 ppb. EPA recorded a violation for haloacetic acids (HAA5) at this utility in 2021. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 75.5 ppb, in 2018, and EPA recorded violations in 2018 and 2019.

What handles it

No certification claim covers this compound yet.

Below EPA’s limits3

Total trihalomethanes (TTHM)

Forms or is added in treatment

Below EPA’s limits

49.7ppb

Highest yearly average, 2020 to 2024

2024 average: 36.1 ppb

Averaged by year, the highest was 49.7 ppb, in 2020, below EPA’s legal limit of 80 ppb. Its highest single sample was 81 ppb. In 2024, the latest year on file, it averaged 36.1 ppb. EPA recorded no violation for total trihalomethanes (TTHM) at this utility since 2020. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 65.6 ppb, in 2015.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Fluoride

Forms or is added in treatment

Below EPA’s limits

0.12ppm

Highest yearly average, 2012 to 2019

2019: not found

Averaged by year, the highest was 0.12 ppm, in 2015, below EPA’s legal limit of 4.0 ppm. In 2019, the latest year on file, it wasn’t found in its one sample.

What handles it

Nitrate

Comes from the source

Below EPA’s limits

0.13ppm

Highest sample; found in 1 of 5

2024: not found

The highest sample, in 2020, was 0.13 ppm, below EPA’s legal limit of 10 ppm. In 2024, the latest year on file, it wasn’t found. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 0.17 ppm, in 2018.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
4 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Arsenic
  • Chromium (total)
  • Lead
  • Uranium

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2021 to Dec. 31, 20210.062 MG/LResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2021 to Sept. 30, 20210.071 MG/LResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2021 to June 30, 20210.071 MG/LResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2021 to March 31, 20210.071 MG/LResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2019 to Sept. 30, 20190.067 MG/LResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2019 to June 30, 201982.5 UG/LResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2019 to March 31, 201970.6 UG/LResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2018 to Dec. 31, 201883.3 UG/LResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2018 to Sept. 30, 201860.8 UG/LResolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record.

What this report can’t tell you

  • Everything else. Haloacetic acids (HAA5), total trihalomethanes (TTHM), nitrate and arsenic results here are New York’s own yearly summaries from 2020 on, with EPA’s national file for 2012 to 2019. Fluoride, chromium (total) and uranium come from EPA’s file alone, which ends in 2019. Pocantico Hills Water District’s own annual report, which it must send you every year, has newer results for those and the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; New York’s yearly summaries cover 2020 to 2024; EPA’s compliance samples are from Sept. 27, 2012 to Nov. 4, 2019.

Testing your own tap

Pocantico Hills Water District’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab New York certifies.

The 3 labs New York certifies closest to the area Pocantico Hills Water District serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Yorktown Medical Laboratory Inc.

    Yorktown Heights, NY · about 7 miles

    Certified for bacteria, nitrate, lead and copper

    (914) 245-3203

  • Westchester Co Labs and Research

    Valhalla, NY · about 8 miles

    Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics, organic chemicals, disinfection byproducts, PFAS

    (914) 231-1768

  • EAS Inc. - Eastern Analytical Services Inc.

    Elmsford, NY · about 11 miles

    Certified for lead and copper, asbestos

    (914) 592-8380

All 161 certified labs for New York

Sources