Skip to content
TapBuff

Chesterfield WD

What EPA’s and New York’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
2,300 people
Connections
1,000
Water source
Surface water
Based in
Chesterfield (T), NY
County
Essex
Owner
Local government
The ZIP code it serves

12944

The short answer

Nothing in EPA’s and New York’s records for this utility is above a health goal. That covers nitrate, arsenic and other regulated chemicals, plus lead and copper, not everything. 6 health-based violations since 2016.

What was found

Copper: EPA’s file records a utility’s copper only when it exceeds the action level. The last here was 2.4 ppm, for the period ending Dec. 31, 1993. None since is on file, so it is not counted as a current finding.

Haloacetic acids (HAA5), total trihalomethanes (TTHM), arsenic, nitrate and uranium: New York’s yearly summaries per water system, 2020 to 2024, with EPA’s 2012 to 2019 file for earlier years.

Fluoride and chromium (total): EPA’s compliance monitoring file, samples taken from July 24, 2012 to April 22, 2019. Newer results are in the utility’s annual water quality report.

Below EPA’s limits3

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

49.9ppb

Highest yearly average, 2020 to 2024

2024 average: 27.1 ppb

Averaged by year, the highest was 49.9 ppb, in 2021, below EPA’s legal limit of 60 ppb. Its highest single sample was 77.9 ppb. In 2024, the latest year on file, it averaged 27.1 ppb. EPA recorded no violation for haloacetic acids (HAA5) at this utility since 2020. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 76.7 ppb, in 2013, and EPA recorded violations in 2012, 2013, 2014, 2015, 2016 and 2018.

What handles it

No certification claim covers this compound yet.

Total trihalomethanes (TTHM)

Forms or is added in treatment

Below EPA’s limits

60.4ppb

Highest yearly average, 2020 to 2024

Averaged by year, the highest was 60.4 ppb, in 2024, below EPA’s legal limit of 80 ppb. Its highest single sample was 106 ppb. That was also the latest year on file. EPA recorded no violation for total trihalomethanes (TTHM) at this utility since 2020. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 76.9 ppb, in 2015, and EPA recorded a violation in 2012.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Fluoride

Forms or is added in treatment

Below EPA’s limits

0.29ppm

Highest yearly average, 2012 to 2019

2019, one sample: 0.23 ppm

Averaged by year, the highest was 0.29 ppm, in 2016, below EPA’s legal limit of 4.0 ppm. In 2019, the latest year on file, its one sample was 0.23 ppm.

What handles it

5 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Arsenic
  • Chromium (total)
  • Lead
  • Nitrate
  • Uranium

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2018 to June 30, 201876.2 UG/LResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2018 to March 31, 201882.3 UG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2016 to Sept. 30, 201662.9 UG/LResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2016 to June 30, 201661 UG/LResolved
Interim Enhanced Surface Water Treatment RuleOne cloudiness reading was above the maximum allowed.EPA: Single Turbidity Exceed (Enhanced SWTR)Feb. 1, 2016 to Feb. 29, 2016—Resolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2016 to March 31, 201660.3 UG/LResolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record.

What this report can’t tell you

  • Everything else. Haloacetic acids (HAA5), total trihalomethanes (TTHM), arsenic, nitrate and uranium results here are New York’s own yearly summaries from 2020 on, with EPA’s national file for 2012 to 2019. Fluoride and chromium (total) come from EPA’s file alone, which ends in 2019. Chesterfield WD’s own annual report, which it must send you every year, has newer results for those and the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; New York’s yearly summaries cover 2020 to 2024; EPA’s compliance samples are from July 24, 2012 to April 22, 2019.

Testing your own tap

Chesterfield WD’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab New York certifies.

The 2 labs New York certifies closest to the area Chesterfield WD serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Endyne Inc. Williston VT

    Williston, VT · about 22 miles

    Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics, organic chemicals, disinfection byproducts

    (802) 879-4333

  • Endyne, Inc.

    Lake George, NY · about 70 miles

    Certified for bacteria, nitrate

    (833) 837-8426

All 161 certified labs for New York

Sources