Skip to content
TapBuff

Riverview Manor Condos

What EPA’s and CDC’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
110 people
Connections
46
Water source
Groundwater
Based in
Raymond, NH
County
Rockingham
Owner
Private
The ZIP code it serves

03077

The short answer

1 result is above EPA’s legal limit, and 1 more is above the health goal. The worst: Arsenic, above the legal limit. 1 health-based violation since 2016.

What handles it

What was found

Lead and copper: lead at 0.51 mg/L (1993) is left out of this report: more than 20 times the action level, it looks like µg/L entered as mg/L.

Copper: EPA’s file records a utility’s copper only when it exceeds the action level. The last here was 2.5 ppm, for the period ending Dec. 31, 1993. None since is on file, so it is not counted as a current finding.

Arsenic, uranium and nitrate: New Hampshire’s yearly averages per water system, as CDC’s Environmental Public Health Tracking Network publishes them, 2020 to 2023, with EPA’s 2012 to 2019 file for earlier years.

Fluoride, total trihalomethanes (TTHM) and chromium (total): EPA’s compliance monitoring file, samples taken from July 15, 2015 to Aug. 8, 2018. Newer results are in the utility’s annual water quality report.

Above the legal limit1

Arsenic

Comes from the source

Above the legal limit

1.8ppb

Highest yearly average, 2021 to 2023

2023 average: 1.7 ppb

Averaged by year, the highest was 1.8 ppb, in 2021: below EPA’s legal limit of 10 ppb, but above its health goal of zero. In 2023, the latest year on file, it averaged 1.7 ppb. EPA judges this limit at each sampling point, and recorded a violation for arsenic at this utility in 2026. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 2.0 ppb, in 2015.

What handles it

  • NSF/ANSI 58 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
  • NSF/ANSI 53 look for “Arsenic (Pentavalent)<=50 ppb Reduction”

Above the health goal1

Uranium

Comes from the source

Above the health goal

16ppb

Highest yearly average, 2021

Averaged by year, the highest was 16 ppb, in 2021: below EPA’s legal limit of 30 ppb, but above its health goal of zero. That is the only year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 13 ppb, in 2015.

What handles it

Below EPA’s limits2

Fluoride

Forms or is added in treatment

Below EPA’s limits

0.15ppm

Highest yearly average, 2015 to 2018

2018: not found

Averaged by year, the highest was 0.15 ppm, in 2015, below EPA’s legal limit of 4.0 ppm. In 2018, the latest year on file, it wasn’t found in its one sample.

What handles it

Total trihalomethanes (TTHM)

Forms or is added in treatment

Below EPA’s limits

1.0ppb

Highest yearly average, 2016 to 2018

2018: not found

Averaged by year, the highest was 1.0 ppb, in 2017, below EPA’s legal limit of 80 ppb. In 2018, the latest year on file, it wasn’t found in its one sample.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
2 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Chromium (total)
  • Nitrate

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

  • NSF/ANSI 53

    Claim: Arsenic (Pentavalent)<=50 ppb Reduction

    For: Arsenic

    Other certifiers’ wording: Arsenic (III) (50 ppb influent level)

  • NSF/ANSI 58

    Claims: Arsenic (Pentavalent)<=50 ppb Reduction, Uranium

    For: Arsenic, Uranium

    Other certifiers’ wording: Arsenic (Pentavalent)<=300 ppb Reduction; Arsenic (V) (300 ppb influent level)

At the tap, or for the whole house?

These come with the water itself, so a whole-house system certified for the same claims treats every tap and shower. A filter at the tap treats drinking water for much less. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

Compare five-year costs

The best reverse osmosis systems, ranked

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2026 to March 31, 20260.011 MG/LArchived
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record.

What this report can’t tell you

  • Everything else. Arsenic, uranium and nitrate results here are New Hampshire’s yearly averages as CDC publishes them, from 2020 on, with EPA’s national file for 2012 to 2019. Fluoride, total trihalomethanes (TTHM) and chromium (total) come from EPA’s file alone, which ends in 2019. Riverview Manor Condos’s own annual report, which it must send you every year, has newer results for those and the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; CDC’s yearly averages for New Hampshire cover 2020 to 2023; EPA’s compliance samples are from July 15, 2015 to Aug. 8, 2018.

Testing your own tap

Riverview Manor Condos’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab New Hampshire certifies.

The 3 labs New Hampshire certifies closest to the area Riverview Manor Condos serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Eurofins Derry

    Derry, NH · about 11 miles

    Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics, organic chemicals, disinfection byproducts, PFAS

    (603) 432-3044

  • Nelson Analytical LLC

    Manchester, NH · about 11 miles

    Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics, organic chemicals, disinfection byproducts

    (603) 622-0200

  • Seacoast Analytical Services LLC

    Lee, NH · about 15 miles

    Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics

    (603) 868-1457

All 63 certified labs for New Hampshire

Sources

PWSID NH1972020. Rebuilt from EPA data on Oct. 18, 2026.