Town of Ferriday Water System water quality report, rewritten
- Serves
- 3,816
- Connections
- 1,272
- Water source
- Groundwater
- Based in
- Ferriday, LA
- County
- Concordia Parish
- Owner
- Local government
The ZIP code it serves
PWSID LA10290052026 edition · EPA data
Read this first
- Lithium (above EPA’s health benchmark) was found in two of 2 samples, highest 19.4 ppb. Above EPA’s health reference level of 10 ppb, a screening level rather than an enforceable limit.
- Lead (above the health goal) In the latest period, 9 in 10 homes sampled were at or below 11.4 ppb, below the 15 ppb action level. The action level drops to 10 ppb on Nov. 1, 2027, and this result is at or above that. EPA’s health goal for lead is zero.
77 health-based violations since 2016. Details are below.
What handles itWhat was found
Highlighted: above the health goal, or EPA’s health benchmark where there is no goal. Circled: above the legal limit in at least one sample, or the action level. Every scale puts that line at its middle.
Lithium (above EPA’s health benchmark)
Comes from the source
19.4ppb
Highest of 2 samples; found in two
Above EPA’s health reference level of 10 ppb, a screening level rather than an enforceable limit.
What handles it
No certification claim covers this compound yet.
EPA UCMR 5, samples taken from March 11, 2024 to Sept. 17, 2024. Each blue tick is one sample where it was found.
Lead (above the health goal)
Comes from pipes, often your own
11.4ppb
90th percentile, 2023 to 2025
In the latest period, 9 in 10 homes sampled were at or below 11.4 ppb, below the 15 ppb action level. The action level drops to 10 ppb on Nov. 1, 2027, and this result is at or above that. EPA’s health goal for lead is zero.
What handles it
- NSF/ANSI 53Look for: Lead Reduction
- NSF/ANSI 58Look for: Lead Reduction
EPA SDWIS, lead and copper monitoring periods ending 2013 to 2025. The pointer marks the latest period; each blue tick is an earlier one.
Tested and not found
Below EPA’s minimum reporting level in every sample taken from March 11, 2024 to Jan. 6, 2025. Not found means not measured above that level, which is not the same as zero.
All 29 compounds tested and not found
- 11Cl-PF3OUdS
- 4:2 FTS
- 6:2 FTS
- 8:2 FTS
- 9Cl-PF3ONS
- ADONA
- HFPO-DA (GenX)
- NEtFOSAA
- NFDHA
- NMeFOSAA
- PFBA
- PFBS
- PFDA
- PFDoA
- PFEESA
- PFHpA
- PFHpS
- PFHxA
- PFHxS
- PFMBA
- PFMPA
- PFNA
- PFOA
- PFOS
- PFPeA
- PFPeS
- PFTA
- PFTrDA
- PFUnA
Violations since 2016
| Contaminant or rule | Type | Period | Measured | Status |
|---|---|---|---|---|
| Groundwater Rule | Required treatment for surface water or groundwater was not met.EPA: Treatment Technique (SWTR and GWR) | March 1, 2026 to March 31, 2026 | — | Archived |
| Groundwater Rule | Required treatment for surface water or groundwater was not met.EPA: Treatment Technique (SWTR and GWR) | Oct. 1, 2025 to Oct. 31, 2025 | — | Archived |
| Groundwater Rule | Required treatment for surface water or groundwater was not met.EPA: Treatment Technique (SWTR and GWR) | Sept. 1, 2025 to Sept. 30, 2025 | — | Archived |
| Groundwater Rule | Required treatment for surface water or groundwater was not met.EPA: Treatment Technique (SWTR and GWR) | Aug. 1, 2025 to Aug. 31, 2025 | — | Archived |
| TTHM | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | July 1, 2025 to Sept. 30, 2025 | 0.081 MG/L | Archived |
| Groundwater Rule | Required treatment for surface water or groundwater was not met.EPA: Treatment Technique (SWTR and GWR) | July 1, 2025 to July 31, 2025 | — | Archived |
| Groundwater Rule | Required treatment for surface water or groundwater was not met.EPA: Treatment Technique (SWTR and GWR) | June 1, 2025 to June 30, 2025 | — | Archived |
| TTHM | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | April 1, 2025 to June 30, 2025 | 0.1 MG/L | Archived |
| TTHM | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Jan. 1, 2025 to March 31, 2025 | 0.1 MG/L | Archived |
| Lead and Copper Rule Revisions | The required inventory of lead service lines was not completed or submitted on time.EPA: LSL Inventory | Oct. 17, 2024 | — | Resolved |
| TTHM | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Oct. 1, 2024 to Dec. 31, 2024 | 0.099 MG/L | Archived |
| TTHM | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | July 1, 2024 to Sept. 30, 2024 | 0.1 MG/L | Archived |
| TTHM | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | April 1, 2024 to June 30, 2024 | 0.1 MG/L | Archived |
| TTHM | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Jan. 1, 2024 to March 31, 2024 | 0.1 MG/L | Archived |
| TTHM | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Oct. 1, 2023 to Dec. 31, 2023 | 0.097 MG/L | Archived |
| TTHM | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | July 1, 2023 to Sept. 30, 2023 | 0.092 MG/L | Archived |
| TTHM | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | April 1, 2023 to June 30, 2023 | 0.097 MG/L | Archived |
| TTHM | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Jan. 1, 2023 to March 31, 2023 | 0.099 MG/L | Archived |
| TTHM | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Oct. 1, 2022 to Dec. 31, 2022 | 0.11 MG/L | Archived |
| Total Haloacetic Acids (HAA5) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Oct. 1, 2022 to Dec. 31, 2022 | 0.062 MG/L | Archived |
| TTHM | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | July 1, 2022 to Sept. 30, 2022 | 0.13 MG/L | Archived |
| Total Haloacetic Acids (HAA5) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | July 1, 2022 to Sept. 30, 2022 | 0.062 MG/L | Archived |
| Groundwater Rule | A significant problem found in a state inspection was not fixed on time.EPA: Failure To Address Deficiency | May 16, 2022 | — | Resolved |
| Groundwater Rule | A significant problem found in a state inspection was not fixed on time.EPA: Failure To Address Deficiency | May 16, 2022 | — | Resolved |
| Total Haloacetic Acids (HAA5) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | April 1, 2022 to June 30, 2022 | 0.07 MG/L | Archived |
| TTHM | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | April 1, 2022 to June 30, 2022 | 0.14 MG/L | Archived |
| Groundwater Rule | Required treatment for surface water or groundwater was not met.EPA: Treatment Technique (SWTR and GWR) | March 1, 2022 to March 31, 2022 | — | Resolved |
| Groundwater Rule | Required treatment for surface water or groundwater was not met.EPA: Treatment Technique (SWTR and GWR) | Feb. 1, 2022 to Feb. 28, 2022 | — | Resolved |
| Total Haloacetic Acids (HAA5) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Jan. 1, 2022 to March 31, 2022 | 0.085 MG/L | Archived |
| TTHM | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Jan. 1, 2022 to March 31, 2022 | 0.14 MG/L | Archived |
| Total Haloacetic Acids (HAA5) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Oct. 1, 2021 to Dec. 31, 2021 | 0.082 MG/L | Archived |
| TTHM | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Oct. 1, 2021 to Dec. 31, 2021 | 0.14 MG/L | Archived |
| TTHM | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | July 1, 2021 to Sept. 30, 2021 | 0.14 MG/L | Archived |
| Total Haloacetic Acids (HAA5) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | July 1, 2021 to Sept. 30, 2021 | 0.087 MG/L | Archived |
| TTHM | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | April 1, 2021 to June 30, 2021 | 0.14 MG/L | Archived |
| Groundwater Rule | Required treatment for surface water or groundwater was not met.EPA: Treatment Technique (SWTR and GWR) | April 1, 2021 to April 30, 2021 | — | Resolved |
| Total Haloacetic Acids (HAA5) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | April 1, 2021 to June 30, 2021 | 0.084 MG/L | Archived |
| Total Haloacetic Acids (HAA5) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Jan. 1, 2021 to March 31, 2021 | 0.078 MG/L | Archived |
| TTHM | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Jan. 1, 2021 to March 31, 2021 | 0.14 MG/L | Archived |
| Total Haloacetic Acids (HAA5) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Oct. 1, 2020 to Dec. 31, 2020 | 0.075 MG/L | Archived |
| Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 53 monitoring or reporting violations not shown. | ||||
What handles it
A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”
- NSF/ANSI 53
Claim: Lead Reduction
For: Lead
- NSF/ANSI 58
Claim: Lead Reduction
For: Lead
At the tap, or for the whole house?
Lead and copper usually come from pipes and fixtures inside or near your home. A whole-house system sits where water enters, so it cannot catch what your own plumbing adds after it. For those, the filter that counts is the one at the tap. How whole-house systems compare.
Filters with those claims on a certifier’s listing
TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money
Brita Tahoe Pitcher with Elite Filter (OB60, OB06)
Pitcher
- WQA listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 401checked Oct. 4, 2026
Certified for: Lead
PUR PLUS 11-Cup Pitcher (PPT111W)
Pitcher
- NSF listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 401checked Oct. 4, 2026
- WQA listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 401checked Oct. 4, 2026
- IAPMO listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 401checked Oct. 4, 2026
Certified for: Lead
ZeroWater 10 Cup Pitcher (ZP-010)
Pitcher
- IAPMO listing:NSF/ANSI 42NSF/ANSI 53checked Oct. 4, 2026
Certified for: Lead
PUR PLUS Faucet Filtration System, Horizontal (PFM400H)
Faucet mount
- NSF listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 401checked Oct. 4, 2026
- WQA listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 401checked Oct. 4, 2026
- IAPMO listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 401checked Oct. 4, 2026
Certified for: Lead
Brita Elite Water Filter Faucet System (SAFF-100/FF-100)
Faucet mount
- WQA listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 401checked Oct. 4, 2026
Certified for: Lead
What this report cannot tell you
- Levels of everything else. Federal bulk data carries results for PFAS, lithium, lead and copper, and violations for the rest. Nitrate, arsenic, disinfection byproducts and other levels are in Town of Ferriday Water System’s own annual report, which it must send you every year.
- Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.
- Anything after the latest data. SDWIS data is from 2026 Q2; UCMR 5 samples are from March 11, 2024 to Jan. 6, 2025.
What to do next
Read up on the 2 marked results
What each one does to health, where it comes from, and the certification claim that addresses it.
Start with LithiumGet the utility’s own report
Town of Ferriday Water System must send you a water quality report every year. It lists nitrate, arsenic and byproduct levels this page cannot.
How to read itTest your own tap for lead
Your service line, solder and fixtures decide the lead at your faucet, not the utility’s average.
Lead in your water: what to doCompare certified filters
What the filters certified for these results cost over five years, cartridges included.
Compare five-year costs
Other Louisiana utilities
- Baton Rouge Water Company596,844
- New Orleans Carrollton Water Works334,903
- E Jefferson Ww District 1275,163
- City of Shreveport Water System192,378
- Lafayette Utilities Water System169,389
- W Jefferson Ww District 2140,264
- Schriever Water Treatment Service Area116,460
- Lafourche Water District 181,609
- City of Bossier City Water System79,506
- City of Lake Charles Water System79,500
- Ward II Water District78,147
- Tangipahoa Parish Water District75,873
Sources
- EPA UCMR 5 occurrence data, file of Aug. 27, 2026
- EPA SDWA bulk download (SDWIS federal data), 2026 Q2
- Limits and goals: each contaminant’s page, with its EPA source.
- How this page is built: methodology.