Skip to content
TapBuff

Pointe A la Hache Water System

What EPA’s and CDC’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
882 people
Connections
256
Water source
Surface water
Based in
Belle Chasse, LA
County
Plaquemines Parish
Owner
Local government
The 3 ZIP codes it serves

70040, 70082, 70083

The short answer

1 result is above EPA’s legal limit, and 2 more are above the health goal. The worst: Total trihalomethanes (TTHM), above the legal limit. 24 health-based violations since 2016.

What handles it

What was found

Total trihalomethanes (TTHM), arsenic, uranium, haloacetic acids (HAA5) and nitrate: Louisiana’s yearly averages per water system, as CDC’s Environmental Public Health Tracking Network publishes them, 2020 to 2022, with EPA’s 2012 to 2019 file for earlier years.

Fluoride and chromium (total): EPA’s compliance monitoring file, samples taken from Feb. 13, 2012 to Feb. 14, 2019. Newer results are in the utility’s annual water quality report.

Above the legal limit1

Total trihalomethanes (TTHM)

Forms or is added in treatment

Above the legal limit

68.7ppb

Highest yearly average, 2020 to 2022

2022 average: 49.2 ppb

Averaged by year, the highest was 68.7 ppb, in 2021, below EPA’s legal limit of 80 ppb. In 2022, the latest year on file, it averaged 49.2 ppb. EPA judges this limit at each sampling point, and recorded a violation for total trihalomethanes (TTHM) at this utility in 2026. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 93.5 ppb, in 2012, and EPA recorded violations in 2012, 2013, 2014 and 2017.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Above the health goal2

Arsenic

Comes from the source

Above the health goal

1.1ppb

Highest yearly average, 2020 to 2022

Averaged by year, the highest was 1.1 ppb, in 2022: below EPA’s legal limit of 10 ppb, but above its health goal of zero. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 6.5 ppb, in 2012.

What handles it

  • NSF/ANSI 58 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
  • NSF/ANSI 53 look for “Arsenic (Pentavalent)<=50 ppb Reduction”

Uranium

Comes from the source

Above the health goal

0.16ppb

Highest yearly average, 2020 to 2022

Averaged by year, the highest was 0.16 ppb, in 2022: below EPA’s legal limit of 30 ppb, but above its health goal of zero. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 0.99 ppb, in 2012.

What handles it

Below EPA’s limits3

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

45.9ppb

Highest yearly average, 2020 to 2022

2022 average: 29.1 ppb

Averaged by year, the highest was 45.9 ppb, in 2021, below EPA’s legal limit of 60 ppb. In 2022, the latest year on file, it averaged 29.1 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 60 ppb, in 2016, and EPA recorded a violation in 2016.

What handles it

No certification claim covers this compound yet.

Nitrate

Comes from the source

Below EPA’s limits

0.9ppm

Highest yearly average, 2022

Averaged by year, the highest was 0.9 ppm, in 2022, below EPA’s legal limit of 10 ppm. That is the only year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 2.1 ppm, in 2016.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”

Fluoride

Forms or is added in treatment

Below EPA’s limits

0.35ppm

Highest yearly average, 2012 to 2019

Averaged by year, the highest was 0.35 ppm, in 2019, below EPA’s legal limit of 4.0 ppm. That was also the latest year on file.

What handles it

2 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Chromium (total)
  • Lead

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

  • NSF/ANSI 53

    Claims: Trihalomethanes (TTHM) Reduction, Arsenic (Pentavalent)<=50 ppb Reduction

    For: Total trihalomethanes (TTHM), Arsenic

    Other certifiers’ wording: VOC Reduction; Arsenic (III) (50 ppb influent level)

  • NSF/ANSI 58

    Claims: Trihalomethanes (TTHM) Reduction, Arsenic (Pentavalent)<=50 ppb Reduction, Uranium

    For: Total trihalomethanes (TTHM), Arsenic, Uranium

    Other certifiers’ wording: Arsenic (Pentavalent)<=300 ppb Reduction; Arsenic (V) (300 ppb influent level)

At the tap, or for the whole house?

These come with the water itself, so a whole-house system certified for the same claims treats every tap and shower. A filter at the tap treats drinking water for much less. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

Compare five-year costs

The best reverse osmosis systems, ranked

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2026 to March 31, 20260.084 MG/LArchived
Total organic carbonNot enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor RemovalJan. 1, 2022 to March 31, 2022—Resolved
Total organic carbonNot enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor RemovalOct. 1, 2021 to Dec. 31, 2021—Resolved
Total organic carbonNot enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor RemovalJuly 1, 2021 to Sept. 30, 2021—Resolved
Total organic carbonNot enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor RemovalApril 1, 2021 to June 30, 2021—Resolved
Total organic carbonNot enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor RemovalJan. 1, 2021 to March 31, 2021—Resolved
Total organic carbonNot enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor RemovalOct. 1, 2019 to Dec. 31, 2019—Resolved
Total organic carbonNot enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor RemovalJuly 1, 2019 to Sept. 30, 2019—Resolved
Total organic carbonNot enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor RemovalJan. 1, 2019 to March 31, 2019—Resolved
Total organic carbonNot enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor RemovalOct. 1, 2018 to Dec. 31, 2018—Resolved
Total organic carbonNot enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor RemovalJuly 1, 2018 to Sept. 30, 2018—Resolved
Total organic carbonNot enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor RemovalApril 1, 2018 to June 30, 2018—Resolved
Total organic carbonNot enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor RemovalJan. 1, 2018 to March 31, 2018—Resolved
Total organic carbonNot enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor RemovalOct. 1, 2017 to Dec. 31, 2017—Resolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2017 to Sept. 30, 201781 UG/LResolved
Total organic carbonNot enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor RemovalJuly 1, 2017 to Sept. 30, 2017—Resolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2017 to June 30, 201782 UG/LResolved
Total organic carbonNot enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor RemovalApril 1, 2017 to June 30, 2017—Resolved
Total organic carbonNot enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor RemovalJan. 1, 2017 to March 31, 2017—Resolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2016 to Dec. 31, 201667 UG/LResolved
Total organic carbonNot enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor RemovalOct. 1, 2016 to Dec. 31, 2016—Resolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2016 to Sept. 30, 201665 UG/LResolved
Total organic carbonNot enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor RemovalApril 1, 2016 to June 30, 2016—Resolved
Total organic carbonNot enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor RemovalJan. 1, 2016 to March 31, 2016—Resolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 4 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Total trihalomethanes (TTHM), arsenic, uranium, haloacetic acids (HAA5) and nitrate results here are Louisiana’s yearly averages as CDC publishes them, from 2020 on, with EPA’s national file for 2012 to 2019. Fluoride and chromium (total) come from EPA’s file alone, which ends in 2019. Pointe A la Hache Water System’s own annual report, which it must send you every year, has newer results for those and the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; CDC’s yearly averages for Louisiana cover 2020 to 2022; EPA’s compliance samples are from Feb. 13, 2012 to Feb. 14, 2019.

Testing your own tap

Pointe A la Hache Water System’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Louisiana certifies.

The 2 labs Louisiana certifies closest to the area Pointe A la Hache Water System serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Curtis Environmental Services, Inc.

    LaPlace, LA · about 52 miles

    Certified for minerals and other inorganics, disinfection byproducts

  • Water Test, Inc.

    Covington, LA · about 63 miles

    Certified for bacteria

    (985) 892-8329

All 48 certified labs for Louisiana

Sources

PWSID LA1075005. Rebuilt from EPA data on Oct. 18, 2026.