Skip to content
TapBuff

Hammock Water Supply

What EPA’s and CDC’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
900 people
Connections
300
Water source
Groundwater
Based in
Gilbert, LA
County
Rapides Parish
Owner
Private
The ZIP code it serves

71438

The short answer

1 result is above EPA’s legal limit, and 1 more is above the health goal. The worst: Copper, above the action level. 11 health-based violations since 2016.

What handles it

What was found

Lead and copper: EPA SDWIS monitoring periods ending 2007 to 2024.

Arsenic, haloacetic acids (HAA5), nitrate and total trihalomethanes (TTHM): Louisiana’s yearly averages per water system, as CDC’s Environmental Public Health Tracking Network publishes them, 2020 to 2022, with EPA’s 2012 to 2019 file for earlier years.

Fluoride, chromium (total) and uranium: EPA’s compliance monitoring file, samples taken from May 14, 2012 to Feb. 1, 2018. Newer results are in the utility’s annual water quality report.

Above the legal limit1

Copper

Comes from pipes, often your own

Above the action level

1.6ppm

90th percentile, 2024

In the latest period, 9 in 10 homes sampled were at or below 1.6 ppm, above EPA’s action level of 1.3 ppm.

What handles it

Above the health goal1

Arsenic

Comes from the source

Above the health goal

1.3ppb

Highest yearly average, 2020 to 2022

Averaged by year, the highest was 1.3 ppb, in 2022: below EPA’s legal limit of 10 ppb, but above its health goal of zero. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 55.8 ppb, in 2012, and EPA recorded violations in 2012, 2013, 2014 and 2015.

What handles it

  • NSF/ANSI 58 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
  • NSF/ANSI 53 look for “Arsenic (Pentavalent)<=50 ppb Reduction”

Below EPA’s limits1

Fluoride

Forms or is added in treatment

Below EPA’s limits

0.4ppm

Highest yearly average, 2012 to 2018

2018 average: 0.21 ppm

Averaged by year, the highest was 0.4 ppm, in 2015, below EPA’s legal limit of 4.0 ppm. Its highest single sample was 0.9 ppm. In 2018, the latest year on file, its two samples averaged 0.21 ppm.

What handles it

6 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Chromium (total)
  • Haloacetic acids (HAA5)
  • Lead
  • Nitrate
  • Total trihalomethanes (TTHM)
  • Uranium

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

  • NSF/ANSI 53

    Claims: Copper Reduction, Arsenic (Pentavalent)<=50 ppb Reduction

    For: Copper, Arsenic

    Other certifiers’ wording: Arsenic (III) (50 ppb influent level)

  • NSF/ANSI 58

    Claims: Copper Reduction, Arsenic (Pentavalent)<=50 ppb Reduction

    For: Copper, Arsenic

    Other certifiers’ wording: Arsenic (Pentavalent)<=300 ppb Reduction; Arsenic (V) (300 ppb influent level)

At the tap, or for the whole house?

Lead and copper usually come from pipes and fixtures inside or near your home. A whole-house system sits where water enters, so it cannot catch what your own plumbing adds after it. For those, the filter that counts is the one at the tap. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

Compare five-year costs

The best reverse osmosis systems, ranked

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
Groundwater RuleA significant problem found in a state inspection was not fixed on time.EPA: Failure To Address DeficiencyOct. 6, 2025—Unaddressed
Groundwater RuleA significant problem found in a state inspection was not fixed on time.EPA: Failure To Address DeficiencyOct. 6, 2025—Resolved
Groundwater RuleA significant problem found in a state inspection was not fixed on time.EPA: Failure To Address DeficiencyOct. 6, 2025—Unaddressed
Groundwater RuleA significant problem found in a state inspection was not fixed on time.EPA: Failure To Address DeficiencyOct. 6, 2025—Resolved
Lead and Copper RuleA required study or plan for corrosion control was not done on time.EPA: OCCT/SOWT Study/RecommendationJuly 11, 2024—Resolved
Lead and Copper RuleA required study or plan for corrosion control was not done on time.EPA: OCCT/SOWT Study/RecommendationNov. 11, 2023—Resolved
Lead and Copper RuleWater chemistry used to keep pipes from corroding was outside the required range.EPA: WQP Entry Point/Tap Treatment Technique Non-ComplianceJuly 1, 2023 to Dec. 31, 2023—Resolved
Groundwater RuleA significant problem found in a state inspection was not fixed on time.EPA: Failure To Address DeficiencyDec. 1, 2020—Resolved
Groundwater RuleA significant problem found in a state inspection was not fixed on time.EPA: Failure To Address DeficiencyDec. 1, 2020—Resolved
Groundwater RuleA significant problem found in a state inspection was not fixed on time.EPA: Failure To Address DeficiencyOct. 17, 2019—Resolved
Groundwater RuleA significant problem found in a state inspection was not fixed on time.EPA: Failure To Address DeficiencyOct. 17, 2019—Resolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 6 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Arsenic, haloacetic acids (HAA5), nitrate and total trihalomethanes (TTHM) results here are Louisiana’s yearly averages as CDC publishes them, from 2020 on, with EPA’s national file for 2012 to 2019. Fluoride, chromium (total) and uranium come from EPA’s file alone, which ends in 2019. Hammock Water Supply’s own annual report, which it must send you every year, has newer results for those and the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; CDC’s yearly averages for Louisiana cover 2020 to 2022; EPA’s compliance samples are from May 14, 2012 to Feb. 1, 2018.

Testing your own tap

Hammock Water Supply’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Louisiana certifies.

The 3 labs Louisiana certifies closest to the area Hammock Water Supply serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • LDH Rapides Regional Laboratory

    Alexandria, LA · about 20 miles

    Certified for bacteria

    (318) 487-5282

  • JRTC & Fort Johnson Environmental Laboratory

    Fort Polk, LA · about 24 miles

    Certified for bacteria

    (337) 531-9128

  • LDH Lake Charles Regional Laboratory

    Lake Charles, LA · about 66 miles

    Certified for bacteria

    (337) 475-3236

All 48 certified labs for Louisiana

Sources

PWSID LA1079030. Rebuilt from EPA data on Oct. 18, 2026.