City of Springhill Water System
What EPA’s and CDC’s records show in this utility’s water: PFAS and lithium; nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.
- Serves
- 7,800 people
- Connections
- 2,600
- Water source
- Groundwater
- Based in
- Springhill, LA
- County
- Webster Parish
- Owner
- Local government
The ZIP code it serves
The short answer
1 result is above EPA’s legal limit, 1 more is above the health goal, and 1 more is above EPA’s health benchmark. The worst: Copper, above the action level. 2 health-based violations since 2016.
What handles itWhat was found
PFAS and lithium: EPA UCMR 5, samples taken from June 11, 2025 to Dec. 15, 2025.
Lead and copper: EPA SDWIS monitoring periods ending 2019 to 2025.
Total trihalomethanes (TTHM), haloacetic acids (HAA5) and nitrate: Louisiana’s yearly averages per water system, as CDC’s Environmental Public Health Tracking Network publishes them, 2020 to 2022, with EPA’s 2012 to 2019 file for earlier years.
Fluoride, arsenic, chromium (total) and uranium: EPA’s compliance monitoring file, samples taken from April 9, 2012 to May 21, 2018. Newer results are in the utility’s annual water quality report.
PFAS: None of the six PFAS in EPA’s 2024 drinking water rule was found in this utility’s samples. None of the other 23 PFAS tested for was found either.
EPA’s 2024 PFAS rule, compound by compound
| PFAS | EPA’s limit | Result |
|---|---|---|
| PFOA | 4.0 ppt | Not foundNot found in any of 8 samples, below 4 ppt |
| PFOS | 4.0 ppt | Not foundNot found in any of 8 samples, below 4 ppt |
| PFHxS | 10 ppt | Not foundNot found in any of 8 samples, below 3 ppt |
| PFNA | 10 ppt | Not foundNot found in any of 8 samples, below 4 ppt |
| HFPO-DA (GenX) | 10 ppt | Not foundNot found in any of 8 samples, below 5 ppt |
| PFBS | Index only | Not foundNot found in any of 8 samples, below 3 ppt |
| Hazard IndexPFHxS, PFNA, HFPO-DA and PFBS together | 1 | Doesn’t applyDoesn’t apply: no sampling location found two or more of the four |
| Results from EPA’s UCMR 5 sampling. “Below” is the lab’s reporting level: a result under it reads as not found, which is not the same as zero. The limits are EPA’s 2024 rule, with compliance due from 2029; EPA has since proposed changes to some of them, explained on each compound’s page. PFBS has no limit of its own and counts only toward the Hazard Index, which adds up the four, each against EPA’s health-based level, from each sampling location’s average, as EPA’s UCMR 5 summary does. It counts only where two or more of the four were found, and is above the limit from 1.5. | ||
Above the legal limit1
Copper
Comes from pipes, often your own
1.5ppm
90th percentile, 2023 to 2025
In the latest period, 9 in 10 homes sampled were at or below 1.5 ppm, above EPA’s action level of 1.3 ppm.
What handles it
- NSF/ANSI 53 look for “Copper Reduction”
- NSF/ANSI 58 look for “Copper Reduction”
Above the health goal1
Lead
Comes from pipes, often your own
1.0ppb
90th percentile, 2026
In the latest period, 9 in 10 homes sampled were at or below 1.0 ppb, below EPA’s action level of 15 ppb. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.
What handles it
- NSF/ANSI 53 look for “Lead Reduction”
- NSF/ANSI 58 look for “Lead Reduction”
Above EPA’s health benchmark1
Lithium
Comes from the source
24.5ppb
Highest sample, June 11, 2025; found in 8 of 8
The highest sample was 24.5 ppb, about 2.5 times EPA’s health reference level of 10 ppb. That is a screening level, not an enforceable limit.
What handles it
No certification claim covers this compound yet.
Below EPA’s limits3
Total trihalomethanes (TTHM)
Forms or is added in treatment
10.3ppb
Highest yearly average, 2020 to 2022
2022 average: 7.1 ppb
Averaged by year, the highest was 10.3 ppb, in 2021, below EPA’s legal limit of 80 ppb. In 2022, the latest year on file, it averaged 7.1 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 33.3 ppb, in 2018.
What handles it
- NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
- NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
Haloacetic acids (HAA5)
Forms or is added in treatment
4.0ppb
Highest yearly average, 2020 to 2022
2022 average: 3.0 ppb
Averaged by year, the highest was 4.0 ppb, in 2021, below EPA’s legal limit of 60 ppb. In 2022, the latest year on file, it averaged 3.0 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 15.8 ppb, in 2018.
What handles it
No certification claim covers this compound yet.
Fluoride
Forms or is added in treatment
0.22ppm
Highest yearly average, 2012 to 2018
2018 average: 0.2 ppm
Averaged by year, the highest was 0.22 ppm, in 2015, below EPA’s legal limit of 4.0 ppm. Its highest single sample was 0.25 ppm. In 2018, the latest year on file, its four samples averaged 0.2 ppm.
What handles it
- NSF/ANSI 58 look for “Fluoride Reduction”
- NSF/ANSI 53 look for “Fluoride”
33 compounds tested and not foundIncluding all six PFAS in EPA’s 2024 rule. Below the reporting level in every sample. Not found is not the same as zero.
From routine monitoring
- Arsenic
- Chromium (total)
- Nitrate
- Uranium
PFAS and lithium, from EPA’s UCMR 5 sampling
- 11Cl-PF3OUdS
- 4:2 FTS
- 6:2 FTS
- 8:2 FTS
- 9Cl-PF3ONS
- ADONA
- HFPO-DA (GenX)
- NEtFOSAA
- NFDHA
- NMeFOSAA
- PFBA
- PFBS
- PFDA
- PFDoA
- PFEESA
- PFHpA
- PFHpS
- PFHxA
- PFHxS
- PFMBA
- PFMPA
- PFNA
- PFOA
- PFOS
- PFPeA
- PFPeS
- PFTA
- PFTrDA
- PFUnA
What handles it
A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”
- NSF/ANSI 53
Claims: Copper Reduction, Lead Reduction
For: Copper, Lead
- NSF/ANSI 58
Claims: Copper Reduction, Lead Reduction
For: Copper, Lead
At the tap, or for the whole house?
Lead and copper usually come from pipes and fixtures inside or near your home. A whole-house system sits where water enters, so it cannot catch what your own plumbing adds after it. For those, the filter that counts is the one at the tap. How whole-house systems compare.
Filters with those claims on a certifier’s listing
Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money
PUR PLUS 11-Cup Pitcher (PPT111W)
Pitcher
- NSF listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 401checked Oct. 4, 2026
- WQA listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 401checked Oct. 4, 2026
- IAPMO listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 401checked Oct. 4, 2026
Certified for: Copper, Lead
Culligan 10-Cup Pitcher with ZeroWater Technology (ZEROP10)
Pitcher
- IAPMO listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 401checked Oct. 9, 2026
Certified for: Copper, Lead
LifeStraw Home 7-Cup Glass Water Filter Pitcher
Pitcher
- WQA listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 401checked Oct. 9, 2026
Certified for: Copper, Lead
Aquasana SmartFlow Reverse Osmosis (AQ-SFRO2)
Under-sink reverse osmosis
- WQA listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 58NSF/ANSI 401checked Oct. 9, 2026
Certified for: Copper, Lead
Brondell Capella RC250 Reverse Osmosis System
Under-sink reverse osmosis
- WQA listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 58NSF/ANSI 401checked Oct. 9, 2026
Certified for: Copper, Lead
Disinfectant
City of Springhill Water System reported disinfecting with chlorine, not chloramine, at all 4 of its sampling points, in its 2025 sampling for EPA.
Chlorine leaves water that sits out for a few days, CDC says. A filter certified for it carries a chlorine claim under NSF/ANSI 42; a shower filter, a free chlorine claim under NSF/ANSI 177. This is what the utility reported for that sampling. Its annual water quality report says what it uses now.
Violations since 2016
| Contaminant or rule | Type | Period | Measured | Status |
|---|---|---|---|---|
| Lead and Copper Rule Revisions | The required inventory of lead service lines was not completed or submitted on time.EPA: LSL Inventory | Oct. 17, 2024 | — | Unaddressed |
| Groundwater Rule | A significant problem found in a state inspection was not fixed on time.EPA: Failure To Address Deficiency | May 1, 2019 | — | Resolved |
| Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 3 monitoring or reporting violations not shown. | ||||
What this report can’t tell you
Everything else. Total trihalomethanes (TTHM), haloacetic acids (HAA5) and nitrate results here are Louisiana’s yearly averages as CDC publishes them, from 2020 on, with EPA’s national file for 2012 to 2019. Fluoride, arsenic, chromium (total) and uranium come from EPA’s file alone, which ends in 2019. City of Springhill Water System’s own annual report, which it must send you every year, has newer results for those and the contaminants this page does not show.
Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.
What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.
Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 samples are from June 11, 2025 to Dec. 15, 2025; CDC’s yearly averages for Louisiana cover 2020 to 2022; EPA’s compliance samples are from April 9, 2012 to May 21, 2018.
Testing your own tap
The lab Louisiana certifies closest to the area City of Springhill Water System serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.
LDH Shreveport Regional Laboratory
Shreveport, LA · about 38 miles
Certified for bacteria
Sources
- EPA UCMR 5 occurrence data, file of Oct. 15, 2026
- EPA SDWA bulk download (SDWIS federal data), 2026 Q3
- CDC Environmental Public Health Tracking Network, yearly averages Louisiana supplied to CDC, 2020 to 2022, read Oct. 8, 2026. TapBuff’s comparisons with EPA’s limits are its own, not CDC’s or Louisiana’s.
- EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, file of Feb. 5, 2024
- Disinfectant: EPA UCMR 5 occurrence data, additional data elements, file of Oct. 15, 2026
- Certified labs: LDH, laboratories certified by Louisiana for drinking water analysis, read Oct. 16, 2026; distances from the Census 2020 ZIP code tabulation area gazetteer
- Limits and goals: each contaminant’s page, with its EPA source.
- How this page is built: methodology.
PWSID LA1119028. Rebuilt from EPA data on Oct. 18, 2026.
What to do next
- Read up on the 3 results above a lineWhat each one does to health, where it comes from, and the certification claim that addresses it.Start with Copper
- Get the utility’s own reportCity of Springhill Water System must send you a water quality report every year. It covers contaminants this page does not show, and has newer results than EPA’s national file for the ones here that come from it.How to read it
- Test your own tap for leadYour service line, solder and fixtures decide the lead at your faucet, not the utility’s average.Lead in your water: what to do
- Compare certified filtersWhat the filters certified for these results cost over five years, cartridges included.Compare five-year costs