Skip to content
TapBuff

Southern Comfort MHP

What EPA’s and Florida’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
112 people
Connections
56
Water source
Groundwater
Based in
Malabar, FL
County
Brevard
Owner
Private
The ZIP code it serves

33763

The short answer

Nothing in EPA’s and Florida’s records for this utility is above a health goal. That covers nitrate, arsenic and other regulated chemicals, plus lead and copper, not everything. 6 health-based violations since 2016.

What was found

Haloacetic acids (HAA5), total trihalomethanes (TTHM), fluoride, nitrate, arsenic, chromium (total) and uranium: Florida’s own results, samples taken from Feb. 20, 2020 to Dec. 10, 2024, with EPA’s 2012 to 2019 file for earlier years.

Below EPA’s limits4

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

46.2ppb

Highest yearly average, 2020 to 2024

Averaged by year, the highest was 46.2 ppb, in 2024, below EPA’s legal limit of 60 ppb. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 53.9 ppb, in 2014.

What handles it

No certification claim covers this compound yet.

Total trihalomethanes (TTHM)

Forms or is added in treatment

Below EPA’s limits

40ppb

Highest yearly average, 2020 to 2024

Averaged by year, the highest was 40 ppb, in 2024, below EPA’s legal limit of 80 ppb. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 90.2 ppb, in 2016, and EPA recorded violations in 2015, 2016 and 2017.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Fluoride

Forms or is added in treatment

Below EPA’s limits

0.26ppm

Highest yearly average, 2024

Averaged by year, the highest was 0.26 ppm, in 2024, below EPA’s legal limit of 4.0 ppm. Its highest single sample was 0.26 ppm. That is the only year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 0.28 ppm, in 2012.

What handles it

Nitrate

Comes from the source

Below EPA’s limits

0.15ppm

Highest sample; found in 2 of 3

2024, one sample: 0.082 ppm

The highest sample, in 2022, was 0.15 ppm, below EPA’s legal limit of 10 ppm. In 2024, the latest year on file, its one sample was 0.082 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 0.26 ppm, in 2014.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
4 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Arsenic
  • Chromium (total)
  • Lead
  • Uranium

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2017 to June 30, 2017102 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2017 to March 31, 201792.2 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2016 to Dec. 31, 201690.2 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2016 to Sept. 30, 2016108 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2016 to June 30, 2016110 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2016 to March 31, 201698.6 UG/LResolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 35 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Haloacetic acids (HAA5), total trihalomethanes (TTHM), fluoride, nitrate, arsenic, chromium (total) and uranium results here are Florida’s own from 2020 on, with EPA’s national file for 2012 to 2019. Southern Comfort MHP’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Florida’s results run from Feb. 20, 2020 to Dec. 10, 2024.

Testing your own tap

Southern Comfort MHP’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Florida certifies.

The 3 labs Florida certifies closest to the area Southern Comfort MHP serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Pace Analytical Services - Tampa

    Oldsmar, FL · about 5 miles

    Certified for bacteria

    (813) 855-1844

  • Eurofins Tampa

    Tampa, FL · about 12 miles

    Certified for bacteria

    (813) 885-7427

  • St. Petersburg Environmental Compliance Division Laboratory

    St. Petersburg, FL · about 15 miles

    Certified for bacteria, nitrate, minerals and other inorganics

    (727) 892-5696

Florida Department of Health Bureau of Public Health Laboratories: Coliform and E. coli testing for private wells at the Jacksonville and Miami labs. Collection kits come from your county health department, and the sample has to reach the lab on ice the same day it is collected. $40 for private testing through the state lab. Well Water Testing, Florida Department of Health.

All 212 certified labs for Florida

Sources

PWSID FL3054015. Rebuilt from EPA data on Oct. 18, 2026.