Skip to content
TapBuff

Riverbend Estates

What EPA’s and Florida’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
200 people
Connections
45
Water source
Groundwater
Based in
Labelle, FL
County
Hendry
Owner
Private
The ZIP code it serves

33974

The short answer

2 results are above EPA’s legal limit, and 1 more is above the health goal. The worst: Total trihalomethanes (TTHM), above the legal limit. 18 health-based violations since 2016.

What handles it

What was found

Lead and copper: EPA SDWIS monitoring periods ending 2010 to 2025.

Copper: EPA’s file records a utility’s copper only when it exceeds the action level. The last here was 1.6 ppm, for the period ending Dec. 1, 2008. None since is on file, so it is not counted as a current finding.

Total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, nitrate, arsenic and chromium (total): Florida’s own results, samples taken from March 26, 2020 to Dec. 12, 2024, with EPA’s 2012 to 2019 file for earlier years.

Above the legal limit2

Total trihalomethanes (TTHM)

Forms or is added in treatment

Above the legal limit

105ppb

Highest yearly average, 2020 to 2024

2024, one sample: 26.4 ppb

Averaged by year, the highest was 105 ppb, in 2020, above EPA’s legal limit of 80 ppb. Its highest single sample was 172 ppb. In 2024, the latest year on file, its one sample was 26.4 ppb. EPA recorded violations for total trihalomethanes (TTHM) at this utility in 2020 and 2021. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 199 ppb, in 2018, and EPA recorded violations in 2018 and 2019.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Haloacetic acids (HAA5)

Forms or is added in treatment

Above the legal limit

49.1ppb

Highest yearly average, 2020 to 2024

2024, one sample: 4.0 ppb

Averaged by year, the highest was 49.1 ppb, in 2020, below EPA’s legal limit of 60 ppb. Its highest single sample was 98.6 ppb. In 2024, the latest year on file, its one sample was 4.0 ppb. EPA judges this limit at each sampling point, and recorded a violation for haloacetic acids (HAA5) at this utility in 2020. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 123 ppb, in 2018, and EPA recorded violations in 2018 and 2019.

What handles it

No certification claim covers this compound yet.

Above the health goal1

Lead

Comes from pipes, often your own

Above the health goal

1.0ppb

90th percentile, 2025

In the latest period, 9 in 10 homes sampled were at or below 1.0 ppb, below EPA’s action level of 15 ppb. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.

What handles it

Below EPA’s limits2

Fluoride

Forms or is added in treatment

Below EPA’s limits

1.1ppm

Highest yearly average, 2024

Averaged by year, the highest was 1.1 ppm, in 2024, below EPA’s legal limit of 4.0 ppm. That is the only year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 0.95 ppm, in 2018.

What handles it

Nitrate

Comes from the source

Below EPA’s limits

0.13ppm

Highest sample; found in 2 of 3

2024: not found

The highest sample, in 2021, was 0.13 ppm, below EPA’s legal limit of 10 ppm. In 2024, the latest year on file, it wasn’t found in its one sample. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 0.34 ppm, in 2019.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
2 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Arsenic
  • Chromium (total)

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

  • NSF/ANSI 53

    Claims: Trihalomethanes (TTHM) Reduction, Lead Reduction

    For: Total trihalomethanes (TTHM), Lead

    Other certifiers’ wording: VOC Reduction

  • NSF/ANSI 58

    Claims: Trihalomethanes (TTHM) Reduction, Lead Reduction

    For: Total trihalomethanes (TTHM), Lead

At the tap, or for the whole house?

Lead and copper usually come from pipes and fixtures inside or near your home. A whole-house system sits where water enters, so it cannot catch what your own plumbing adds after it. For those, the filter that counts is the one at the tap. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

Compare five-year costs

The best water filters for lead, ranked

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2021 to Sept. 30, 2021104 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2021 to June 30, 202185.8 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2021 to March 31, 2021116 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2020 to Dec. 31, 2020105 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2020 to Sept. 30, 2020103 UG/LResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2020 to June 30, 202068.4 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2020 to June 30, 2020169 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2020 to March 31, 2020126 UG/LResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2019 to Dec. 31, 201967.4 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2019 to Dec. 31, 2019151 UG/LResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2019 to Sept. 30, 201988.7 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2019 to Sept. 30, 2019164 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2019 to June 30, 2019144 UG/LResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2019 to June 30, 201989.4 UG/LResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2019 to March 31, 201987.8 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2019 to March 31, 2019144 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2018 to Dec. 31, 201899.7 UG/LResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2018 to Dec. 31, 201861.4 UG/LResolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 21 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, nitrate, arsenic and chromium (total) results here are Florida’s own from 2020 on, with EPA’s national file for 2012 to 2019. Riverbend Estates’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Florida’s results run from March 26, 2020 to Dec. 12, 2024.

Testing your own tap

Riverbend Estates’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Florida certifies.

The 3 labs Florida certifies closest to the area Riverbend Estates serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Advanced Environmental Laboratories, Inc. - Fort Myers

    Fort Myers, FL · about 7 miles

    Certified for bacteria, minerals and other inorganics

    (239) 674-8130

  • Eurofins Ft. Myers

    Ft. Myers, FL · about 7 miles

    Certified for bacteria

    (239) 590-0337

  • FL Dept. of Health - Lee County Health Department

    Ft. Myers, FL · about 17 miles

    Certified for bacteria

    (239) 274-2200

Florida Department of Health Bureau of Public Health Laboratories: Coliform and E. coli testing for private wells at the Jacksonville and Miami labs. Collection kits come from your county health department, and the sample has to reach the lab on ice the same day it is collected. $40 for private testing through the state lab. Well Water Testing, Florida Department of Health.

All 212 certified labs for Florida

Sources

PWSID FL5264054. Rebuilt from EPA data on Oct. 18, 2026.