Skip to content
TapBuff

Mountview Apartments

What EPA’s and CDC’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
105 people
Connections
35
Water source
Groundwater
Based in
Montville, CT
County
New London
Owner
Private
The ZIP code it serves

06382

The short answer

Nothing in EPA’s and CDC’s records for this utility is above a health goal. That covers nitrate, arsenic and other regulated chemicals, plus lead and copper, not everything. 7 health-based violations since 2016.

What was found

Copper: EPA’s file records a utility’s copper only when it exceeds the action level. The last here was 1.4 ppm, for the period ending June 30, 2009. None since is on file, so it is not counted as a current finding.

Nitrate, arsenic and uranium: Connecticut’s yearly averages per water system, as CDC’s Environmental Public Health Tracking Network publishes them, 2020 to 2023, with EPA’s 2012 to 2019 file for earlier years.

Chromium (total) and fluoride: EPA’s compliance monitoring file, samples taken from June 21, 2012 to Dec. 26, 2018. Newer results are in the utility’s annual water quality report.

Below EPA’s limits2

Nitrate

Comes from the source

Below EPA’s limits

3.7ppm

Highest yearly average, 2020 to 2023

2023 average: 2.2 ppm

Averaged by year, the highest was 3.7 ppm, in 2022, below EPA’s legal limit of 10 ppm. In 2023, the latest year on file, it averaged 2.2 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 3.6 ppm, in 2014.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”

Chromium (total)

Comes from the source

Below EPA’s limits

1.0ppb

Highest yearly average, 2012 to 2018

Averaged by year, the highest was 1.0 ppb, in 2018, below EPA’s legal limit of 100 ppb. That was also the latest year on file.

What handles it

4 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Arsenic
  • Fluoride
  • Lead
  • Uranium

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
Lead and Copper Rule RevisionsThe required inventory of lead service lines was not completed or submitted on time.EPA: LSL InventoryOct. 17, 2024—Unaddressed
Groundwater RuleA significant problem found in a state inspection was not fixed on time.EPA: Failure To Address DeficiencyApril 13, 2023—Resolved
Revised Total Coliform RuleColiform or E. coli results required a detailed review of the system, and it or its fixes were not done on time.EPA: Treatment Technique, Level 2 Assessment (RTCR)Jan. 13, 2021—Resolved
Revised Total Coliform RuleColiform or E. coli results required a detailed review of the system, and it or its fixes were not done on time.EPA: Treatment Technique, Level 2 Assessment (RTCR)Dec. 22, 2020—Resolved
Revised Total Coliform RuleColiform or E. coli results required a detailed review of the system, and it or its fixes were not done on time.EPA: Treatment Technique, Level 2 Assessment (RTCR)Sept. 7, 2017—Resolved
Groundwater RuleFailure To Address ContaminationFeb. 26, 2017—Resolved
Revised Total Coliform RuleE. coli was confirmed in the water system.EPA: Maximum Contaminant Level Violation, E. coli (RTCR)Oct. 1, 2016 to Oct. 31, 2016—Resolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 24 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Nitrate, arsenic and uranium results here are Connecticut’s yearly averages as CDC publishes them, from 2020 on, with EPA’s national file for 2012 to 2019. Chromium (total) and fluoride come from EPA’s file alone, which ends in 2019. Mountview Apartments’s own annual report, which it must send you every year, has newer results for those and the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; CDC’s yearly averages for Connecticut cover 2020 to 2023; EPA’s compliance samples are from June 21, 2012 to Dec. 26, 2018.

Testing your own tap

Mountview Apartments’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Connecticut certifies.

The 3 labs Connecticut certifies closest to the area Mountview Apartments serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Eastern Analytical Laboratory, Inc.

    Old Saybrook, CT · about 18 miles

    Certified for bacteria, nitrate, metals, minerals and other inorganics

    (860) 388-2378

  • CorrTech Corrosion Laboratory

    Deep River, CT · about 20 miles

    Certified for minerals and other inorganics

    (860) 526-2610

  • Environmental Consulting Lab

    Madison, CT · about 27 miles

    Certified for bacteria, nitrate, metals, minerals and other inorganics, radioactivity

    (203) 245-0568

All 86 certified labs for Connecticut

Sources